The Woodward 723 Digital Control can be programmed to suit applications requiring two magnetic pickups or proximity switches as the hardware includes two speed inputs. It also includes four analogue inputs, three analogue outputs, eight discrete inputs and three discrete outputs, all of which can be programmed to satisfy the application.
The control can be used in load sharing systems
The 723 control requires the following power supply input voltages, with 40 watts as the nominal power consumption at rated voltage:
• 18–40 Vdc (24 or 32 Vdc nominal)—low voltage controls
• 90–150 Vdc (125 Vdc nominal)—high voltage controls